Extra Functions
(Only available if the corresponding Extra function was selected in the Service menu)
2.11 Thermostat Function
2.11.1 Start
When the water temp. at the location of T3 drop below this setting P3 will start.
2.11.2 Hysteresis
When the water temp. at the location of T3 exceeds the Start temperature plus the Hysteresis setting, P3 will
shutoff.
2.12 Cooling Function
2.12.1 Cooling start
When the water temp. in the top of system tank (T3) is above this setting P3 will start
2.12.2 Cooling hysteresis
When the water temp. at the top of system tank (T3) falls below the Start temperature minus the Hysteresis setting
P3 will shutoff
2.13 Diffcontrol Function
2.13.1 Max cold tank
When the temp. at the top of the external tank (T3) is above this setting P3 will shutoff
2.13.2 Min warm tank
When the temp. at the top of the system tank (T4) is above this setting P3 will start
2.13.3 Max cold tank
When the temp. at the top of the system tank (T3) is above this setting P3 will shutoff
2.13.4 Min warm tank
The temp. at the top of the external tank (T4) is above this setting P3 will start
2.13.5 dTMax
Temperature difference (ΔT) between the tank designated as cold storage (TC) and the one designated as warm
storage (TW) at which P3 will start
2.13.6 dTMin
Temperature difference (ΔT) between TC and TW at which P3 shutoff
3 Operation
3.1 Automatic and Off operation
To turn ON the system, change the setting to AUTOMATIC
3.2 Manual testing operation
This mode allows you to check the performance of all pumps, valves and sensors
4 Operation Hours
This menu offers both a data view and a graph view for the Operation, dT, Power and Energy values.
Operation
Displays data and graph view of operation hours
dT
Displays data and graph view of temperature differential
Power
Displays data and graph view of kBTU/hour
Energy
Displays data and graph view of kBTU
4.1 SD Card option
To store data and transfer system settings from your PC to the Solar Control
5 Temperatures
This menu displays the temperatures of all connected sensors.
T1 – Collector
Displays the temperatures of collector1 sensor
T2 – Collector2
Displays the temperatures of collector2 sensor
Tank1 bottom
Displays the temperatures of tank bottom sensor
Tank top
Displays the temperatures of tank top sensor
6.7. Controller Display & Operation