Function
Description
1.14. Pump P1
Set to PhAC SC, which is variable speed pump control
1.15. Pump P2
Set to No SCPh, which is not a non-variable speed pump
1.6.4. Freeze Protection
Will keep the solar panel temperature above the Freeze Protection
Temperature setting level by activating the solar pump. Set to 35
°
F
2.1. Maxtemp tank1
Maximum allowed temperature in tank 1 (T2) during normal operation
2.2. dTMax tank1
Difference (ΔT) between collector temperature (T1) and tank1 temperature
(T2) that will automatically engage pump1. Set to 14
°
F
2.3. dTMin tank1
Difference (ΔT) between collector temperature (T1) and Tank1 temperature
(T2) that will automatically disengage pump1. Set to 4
°
F
2.10. Mintemp Collector
Select the minimum collector temperature required for system start-up. Set to
85
°
F
2.11.1. Thermostat Start
When the water temp. at the location of T3 drop below this setting P3 will start.
2.11.2. Hysteresis
When the water temp. at the location of T3 exceeds the Start temperature plus
the Hysteresis setting, P3 will shutoff.
8.11. Replace Front Case
Push the front case into place while making sure to feed the pump power cable through the hole into the
controller enclosure. The casing will simply lock into place.
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 70 of 129