7. Closed Loop Pump Station Installation
󱚡 NOTICE
The following instructions are specific to the Apricus Closed Loop Pump Station, which is
designed for use in Apricus OG-300 certified closed loop systems.
7.1. Design
a) The Apricus Closed Loop Pump Station (ACLPS) is specifically designed for use with the Apricus solar
collector in a closed loop format. It is NOT suitable for direct flow or drain-back systems.
b) The ACLPS has the following key features:
3 Speed Grundfos pump (integrated check valve) Controller mounted directly into pump station
Controller mounted directly into pump
station Flow meter with built in balancing
valve
Purge and fill valve assembly in return
line 3/4” Quick connector push fittings
I n t e g r a t e d a u t o m a t i c a i r
remover Pressure &
temperature gauge
Supplied as standard
with a 4.5 gallon expansion tank and mounting/
connection assembly
7.2. Closed Loop Pump Station Technical Data
Pump Station Format
Closed Loop
Overall Depth
8.375” / 213 mm (With Insulated Cover)
Overall Height
24.5” / 622 mm
Overall Width
17.5” / 444 mm
Weight (Empty)
26 lb. / 11.8 kg.
Solar Connection
¾” (” OD copper) Quick Connect Fitting
Tank Connection
¾” (” OD copper) Quick Connect Fitting
Pressure Relief Valve Connection
3/4” FPT
Pressure Relief Valve Pressure
75psi / 5.1bar
Max. Operating Pressure
50psi / 3.4bar
Max. Operating Temperature
230°F / 110°C
Apricus Solar Collector Installation & Operation Manual - USA
Copyright © 2011 – Apricus Inc Doc: A7-05.4.12-PB Page 53 of 129